AUTOMATIC MANIFOLD CONTROL PANEL
Description: High Pressure Reducer Unit reduces the pressure of gas come from collector which is mounted to the cylinders. The pressure of gas in collectors (150 bar-MPa-2176 psi) is reduced to 4-7 bar that is appropriate pressure to provide for patients and medical devices through pipeline systems.
Areas of use: High Pressure Reducer is used where high pressure gas is needed to control and reduce for service gas pressure value ranges.
Technical Specifications
Product Code: MG-YBDNxx:O (Oxygen), A (N2O), SA (Pure Nitrogen), AR (Argon), KG (Mixed Gas), K (CO2), HD (Hydrogen), H (Dry air) HE (Helium),AT (Acetylene), EO (Ethylene Oxide)
Product Name : Full Automatic High pressure Reducer
Input Pressure: Max. 220 Bar
Output Pressure: 4-7 Bar.
Capacity :150m3/h
Input Point : 4 (Main ramp, Backup Ramp, External Supply, Emergency Case Supply Unit
Operating Temp : (+10)-(+45) C°
Power Supply :220 V 50 Hz 100 Watt
Packaging Type :Carton Box
Package Sizes :118 x 67 x 24 cm
Product Weight :45 Kg
Alarm System : Digital LCD, Alarm, Sound
Installation Space:Installation Space should be airy and determined according to the capacity of cylinders. Electric transformers, generators, oil vapors and boilers should not be installed in the same area. Oxygen plant should not be installed in the same space if there are any oil systems vacuum pumps, and air plants. Only trained people may set up and installed the systems.